multi parameter water quality analyzer
pH/Redox Controller
innoCon 6800P
HOME PRODUCS PARAMETERS pH/Redox pH/Redox Controller pH/Redox Controller innoCon 6800P


pH/Redox Controller innoCon 6800P
pH/Redox Controller innoCon 6800P

pH/Redox Controller innoCon 6800P


The innoCon 6800 plus intelligent controller is designed for water treatment and industrial process monitoring, with Chinese/English menus, automatic 

temperature compensation, two 4-20mA/RS485 Modbus RTU and Hi/Lo alarm outputs as standard, panel and wall mounting. Different water quality 

parameters can be measured by selecting different innoSens electrodes. 



Product Features:


2 sets relay output can set High/ Low 

Automatic cleaning relay output 

2 channel 4-20mA current 

RS485 Modbus output

  • Item No.innoCon 6800P
    MeasurementpH/ORP
    Range-2.00 – 16.00pH;-2000 – 2000mV
    Resolution0.01pH/1mV
    Accuracy±0.01pH/±1mV
    CompensationPT1000 or NTC10K
    DisplayBig-size screen of crystal display, white back light
    languageChinese / English
    PasscodeSet mode: 0022,Calibration mode: 0011
    Power supply90 – 260V AC, 50/60Hz; 24VDC(Optional)
    Current output2x Isolated 4-20mA outputs,programmable measured value and temperature, max. load 500Ω
    Digital communicationRS485 Modbus RTU
    Alarm output2 sets of programmable Hi/Lo contacts with hysteresis setting, 5A/250VAC/30VDC
    Washing RelayWash interval: 0.1-1000h,Wash time:1-1000s
    Working temperature0~70.0℃
    Protection classIP65
    InstallationWall/Pipe/Panel Mounting:144 × 144 × 110mm,Panel Cut Size:138 × 138mm
    SizeDimensions
    WeightCa.0.85Kg
    Order No.33-6801-10


  • innoSens 120 pH Sensor
    Measuring Range0-14pH
    Working temp-5-100℃
    Max. work pressure6bar
    MaterialGlass
    ElectrolytePolymer
    DiaphragmPTFE Diaphragm
    Diameter/Length12mm/120mm
    Threaded PG13.5
    Cable length5m standard
    Applicationsewage,>150μS/cm
    innoSens 125T pH/T Sensor
    Measuring Range0-14pH
    Working temp-5-100℃
    Max. work pressure6bar
    MaterialGlass
    ElectrolytePolymer
    DiaphragmPTFE Diaphragm
    Diameter/Length12mm/120mm
    Threaded PG13.5
    Cable length5m standard
    Applicationsewage,>150μS/cm
    innoSens 130 pH Sensor
    Measuring Range0-14pH
    Working temp-5-135℃
    Max. work pressure10bar
    MaterialGlass
    ElectrolytePolymer
    DiaphragmPTFE Diaphragm
    Diameter/Length12mm/120mm
    Threaded PG13.5
    Cable lengthPurchase separately
    Applicationsewage,>50μS/cm
    innoSens 145T Pure water pH/T Sensor
    Measuring Range0-14pH
    Working temp-5-100℃
    Max. work pressure6bar
    MaterialGlass
    ElectrolyteGel
    DiaphragmCeramic Diaphragms
    Diameter/Length12mm/120mm
    Threaded PG13.5
    Cable length5m standard
    Application>0.1µS/cm Pure water
    innoSens 150T Hydrofluoric acid resistant PH Sensor
    Measuring Range0-14pH
    Working temp-5-100℃
    Max. work pressure6bar
    MaterialGlass
    ElectrolyteGel
    DiaphragmCeramic Diaphragms
    Diameter/Length12mm/120mm
    Threaded PG13.5
    Cable length5m standard
    ApplicationSuitable for< 1000 ppm HF
    innoSens 160T Chlor-alkali chemical pH/T Sensor
    Measuring Range0-14pH
    Working temp-5-100℃
    Max. work pressure6bar
    MaterialGlass
    ElectrolyteGel
    DiaphragmCeramic Diaphragms
    Diameter/Length12mm/120mm
    Threaded PG13.5
    Cable length5m standard
    Application>50µS/cm
    innoSens 210 ORP Sensor
    Measuring Range-2000-2000mV
    Working temp-5-100℃
    Max. work pressure6bar
    MaterialGlass
    ElectrolytePolymer
    DiaphragmPTFE Diaphragm
    Diameter/Length12mm/120mm
    Threaded PG13.5
    Cable length5m standard
    Applicationsewage


  • 33-6801-10  innoCon 6800P pH/Redox controller, 90 – 260V AC
    33-6801-14   innoCon 6800P pH/Redox controller, 24V DC



Datasheet Download






Online Message
We will manage and protect the privacy of the personal information
  • Name
  • E-Mail
  • Telephone
  • Message Content

footer_background
Service Repair Form
Tell us what issue you encountered, including any steps or symptoms.
  • Name
  • Email
  • Phone
  • Fault Description

If you are interested in our products, you can choose to leave your information here, and we will be in touch with you shortly.